EGE-Elektronik Spezial-Sensoren GmbH • http://www.ege-elektronik.com
1.42 E11011
Design SDV 652/1 GAPP
Dimensions
Working range [l/min] 2...20
Maximum flow [l/min] 25
Precision 15...50 °C
<
2%, 5...60 °C
<
4%
Outer diameter pipe [mm] 10
Pipe connection tube fittings for steel tubes according to DIN 2391 / ISO 3304
Output
PNP NC / NO, programmable 4...20 mA, linear
ID-No. P11319
Type SDV 652/1 GAPP
Switching current [mA] 200
Load R
L
[] 200...500
Supply voltage [V] 24 DC ±10%
Current consumption [mA]
<
100
Ambient temperature [°C] 0...+60
Medium temperature [°C] 5...+60
Start-up time [s] 4.5...8
Reaction time [s] 0.5...4
Programmable functions switching point, hysteresis, switching output, time on/off delay
averaging, access code
Compressive strength [bar] 10
Material housing: PBT sensor: PVDF, connection AISI 316 Ti
Protection [EN 60529] IP 65
Connection M12 connector
Notice:
Process-connection in PTFE
available
Accessories mounting plate, connecting cable type SLG (page 1.78), adapter G1/4 (page 1.82)
Series SDV - Vortex flow measuring device
Flow measuring of water
Deviation 2% of terminal value
Programmable
Analog and PNP output
Optional: mounting plate (Z01178)
Flow Sensors
Vortex-Measuring device • Digital display
(2) WH
L+
L-
RL
(1) BN
(4) BK
(3) BU
(4...20 mA)
100
63
63
53
24
Ø 4,5 (4x)
3
4 x
100
43
M12x1
70