EGE-Elektronik Spezial-Sensoren GmbH • http://www.ege-elektronik.com
Design SDI... GAPP
Dimensions
Working range [l/min] 0...40 0.2...80
Measurement error 0...5.0 l/min 0.1 l/min 0...10.0 l/min 0.2 l/min
5...40 l/min 2% of measurement value * 10.1...80 l/min 2% of measurement value *
ID-No. P11320 P11321
Typ
SDI 852/1 GAPP SDI 852/2 GAPP
Outer diameter pipe [mm] 10 15
Pipe connection tube fittings for steel tubes according to DIN 2391 / ISO 3304
Output
PNP NC / NO, programmable 4...20 mA, linear
Switching current [mA] 200
Load R
L
[] 200...500
Supply voltage [V] 24 DC ±10%
Current consumption [mA] 100
Ambient temperature [°C] 0...+60
Medium temperature [°C] 5...+60
Medium conductivity [μS/cm] 10 (water: 15) 20 (water: 30)
Reaction time [s] 0.5...8
Programmable functions switching point, hysteresis, switching output, time on/off delay
analog range, impulse, averaging, access code
Compressive strength [bar] 10
Material housing: PBT sensor: PVDF / AISI 316 Ti
Protection [EN 60529] IP 65
Connection M12 connector
*Notice:
Reference conditions
according to EN 29104
Accessories mounting plate, connecting cable type SLG (page 1.78), adapter G1/4 (page 1.82)
Optional: mounting plate (Z01178)
Series SDI - Magnetic flowmeter
Measurement error < 2%
Programmable
Analog and PNP output
Flow Sensors
Magnetic flowmeter • Digital display
E11011 1.43
(2) WH
L+
L-
RL
(1) BN
(4) BK
(3) BU
(4...20 mA)
100
63
63
53
24
Ø 4,5 (4x)
3
4 x
100
43
M12x1
70
Comentarios a estos manuales